DTL Overcurrent Relay – OA703
-
DTL
Relay
-
Mounting
Flush
-
MTB
ANSI 86 Lockout
-
Setting
Knob adjustment

Built for Safety
-
- Flame Retardant material tested against UL94v-0 fire standards
-
- MTB ANSI 86 Lockout Relay
-
- Enhanced test trip function prevents accidental activation of the relay’s ‘Test Trip’ command

MTB
MTB or Mechanical Trip Button is a proprietary lockout feature that prevents an operator from re-energizing the circuit breaker before isolating the fault and resetting the MTB.
When activated, the MTB latches the output contacts and continues to indicate the presence of a fault until it is cleared, and the relay reset. All these are achieved without the need for an auxiliary power supply to the relay.
LEARN MORE
Protection Degree
IP31 (front) and IP20 (rear). IP65 optional.
Tested in accordance with IEC standards
Product safety, EMC compatibility, environmental, vibration, shock and bump tests.
-
EMC
Compatibility
-
Product
Safety
-
Environmental
Test
-
Vibration, Shock, Bump
Test

Technical Data
-
Power Supply
AC/DC 85-265V (other voltage available)
-
MTB Fault Indication System
ANSI 86 Lockout Relay
-
Product Safety Requirements
IEC 60255-27
-
Overcurrent Setting
2 – 7A
-
Self Check
Self-diagnostic and auto-restore
-
Electromagnetic Compatibility
IEC 60255-26
-
Self-diagnostic and auto-restore
0 – 1 sec
-
Event Records with data/time stamping
20 tripping events, 40 operation logs
-
Cyclic Temperature with Humidity
IEC 60255-1
-
Reset Current Value
≤ 90% of operating value
-
Output Contact
1 x Changeover (C/O)
1 x Normally Open (N/O) -
Vibration, Shock and Bump
IEC 60255-21-1
IEC 60255-21-2 -
Overcurrent withstandability
10 * fault current for 1 sec
-
Protection Class
IP 31 (front), IP20 (rear)
-
Safety
CE Marking